Rockwell Automation Publication 6000-UM001B-EN-P - October 2014 63
Parameters and Function Codes Chapter 4
T Parameters
Parameter
Number
Description Default
Value
Modify
Root
Lower
Limit
Upper
Limit
T01 Fault-To-Bypass
0: Disable
1: Enable
0ON01
T02 Fault-To-Bypass Delay 3 ON 0 60
T03 Fault-To-Bypass Delay When Starting
the Motor (0...60s)
60 ON 0 60
T04 Fault-To-Bypass Minimum Frequency
0...Rated Frequency (Hz)
5ON0Rated
Frequency
T05 Auto Restart After Input Supply Power Loss
0: Disable
1: Enable
0ON01
T06 Input Supply Power Loss Time for
Auto Restart (0...20s)
20 ON 0 20
T07 Local Frequency Command Selection
0: Digital
1: Analog
0ON01
T08 Remote Frequency Command Selection
1: Analog
2: 4-Step Speed
4: Communication Port
1ON14
T09 Frequency Step For Accel or Decel 1 ON 1 Rated
Frequency
T10 Exit Config Environment Password 555 OFF
T11 Automatic Bypass-To-Drive or
Drive-To-Bypass Selection
T12 PID Parameter Settings
P 0.01 ON 0 32767
I 0.01 ON 0 32767
D 0 ON 0 32767
D Gain 0 ON 0 32767
T13 4-Step Variable Speed
(available only when T8=2)
Speed 1 10 ON 0 Rated
Frequency
Speed 2 20 ON 0 Rated
Frequency
Speed 3 30 ON 0 Rated
Frequency
Speed 4 40 ON 0 Rated
Frequency