Rockwell-automation 6012DB PowerFlex Medium Voltage Variable Frequency Instrukcja Użytkownika Strona 89

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 138
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 88
Rockwell Automation Publication 6000-UM001B-EN-P - October 2014 89
Preventative Maintenance and Component Replacement Chapter 5
Replace Door Position Limit Switch
1. Open the drive cabinet door.
2. Disconnect the aviation plug from the back of the Limit Switch.
3. Remove two M4 x 35 bolts and hardware from the mounting bracket.
4. Install the new Limit Switch in reverse order of removal.
Figure 29 - Replace Door Position Limit Switch
ATTENTION: Ensure the input circuit breaker feeding the drive is open. Lock out
and tagout the input circuit breaker before performing any work on the drive or
bypass units.
Nut
Lock washer
Washer
M4 x 35 Bolt
Aviation Plug
Przeglądanie stron 88
1 2 ... 84 85 86 87 88 89 90 91 92 93 94 ... 137 138

Komentarze do niniejszej Instrukcji

Brak uwag