Demo Unit User Manual (AADvance Controller)
4-12
Document: 553850 Issue 1.2: March 2011
About T9110 Processor Variables
The T9110 processor module provides a number of status and control variables that
are available to the application. Status variables retrieve status information; control
variables set status information.
The 9110 Variables Editor presents the variables in seven collections, which it calls
'racks':
Status Integers and Status Booleans, which provide information about the
controller to the application;
Control Integers and Control Booleans, which enable the application to send
specific information to the controller;
RTC Status variables, which provide information about the controller real-time
clock to the application;
RTC Program variables, which specify parts of the date to be written to the
real-time clock;
RTC Control variables, which set and control updates to the real-time clock.
Wire Processor Variables
To wire a 9110 processor variable do the following:
1) Select the Variables tab of the 9110 Processor Editor.
The 9110 Variables Editor dialog box opens.
2) Select a rack, e.g. Status Registers.
The editor displays a list of associated channel variables.
3) Select a Channel.