Demo Unit User Manual (AADvance Controller)
5-6
Document: 553850 Issue 1.2: March 2011
Move a Module to a Different Slot
To move an assigned module to a different slot do the following:
1) Select the Equipment tab.
2) Right-click to select the Move To option.
3) Move the cursor to the right and select the IO Bus 1 Position you want to move
to.
The module is automatically re-assigned to the selected slot.
Note: The channel variable wiring will move with the module to the new slot and is
automatically renumbered.
Configure the I/O Module Process Safety Time
When you configure the process safety time for an I/O module, you can choose to
inherit the top-level value set for the processor or specify a value for the I/O module.
To define the I/O module process safety time do the following:
1) Select a module from the I/O Bus.
2) Put a tick in the Inherit box to inherit the top-level Process Safety Time; or
3) De-select the Inherit box and enter a value into the Process Safety Time field.