Demo Unit User Manual (AADvance Controller)
4-20
Document: 553850 Issue 1.2: March 2011
Processor Module C 24V2 Power Feed Health
Direction: input to application from controller
Type: boolean
Values:
TRUE = power feed voltage is within specification (18 to 32V dc).
FALSE = power feed is outside specification.
Description:
Reports the health of power feed 2 (nominal 24V dc) to the 9110 processor module in
the given slot.
Processor Module A Ready
Direction: input to application from controller
Type: boolean
Values:
TRUE = The 9110 processor module in the given slot is synchronized (see
description)
FALSE = The processor module is out of synchronization or missing.
Description:
Reports that a processor module within a dual or triple modular redundant
configuration is present and is synchronized with one or both of its peers. Reports that
a simplex processor module is present.
Processor Module B Ready
Direction: input to application from controller
Type: boolean
Values:
TRUE = The 9110 processor module in the given slot is synchronized (see
description)
FALSE = The processor module is out of synchronization or missing.
Description:
Reports that a processor module within a dual or triple modular redundant
configuration is present and is synchronized with one or both of its peers. Reports that
a simplex processor module is present.