20 Installation
ATTENTION: Do not make any connections to F1 and
F2 when using a permanent magnet motor. The field
output is for shunt wound motors only. See Table 2 for
field output connections.
Table 2. Field Output Connections
Line Voltage Approximate Connect Motor
(VAC) Field Voltage (VDC) Field To
115 50 F1 and L1
115 100 F1 and F2
230 100 F1 and L1
230 200 F1 and F2
Field output