Store and load a project by using a memory card Chapter 1
This section explains how to store a project on the memory card of the controller.
ATTENTION: During a store operation, all active servo axes are turned off. Before you store a project,
make sure that this does not cause any unexpected movement of an axis.
Before you store the project:
Make all the required edits to the logic.
Download the project to the controller.
Schedule your ControlNet networks.
Follow these steps to store a project.
1. Go online with the controller.
2. Put the controller in Program Mode (Rem Program or Program).
3. On the Online toolbar, click the Controller Properties icon.
Tip:
For 1756-L7x controllers only, Energy Storage instead of Battery OK appears beside the Controller
Properties icon. See the ControlLogix System User Manual, publication 1756-UM001
for information on
the Energy Storage Module.
4. On the Controller Properties dialog box, click the Nonvolatile Memory
tab and then click Load/Store.
Store a project
Rockwell Automation Publication 1756-PM017F-EN-P October 2014 15