Rockwell-automation MPP Processor Moduile Instrukcja Użytkownika Strona 12

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 25
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 11
12
MPP
October
200
5
Issue 6
Triguard
SC300E
Commanded
output
states
are
received
by
an
output
module’s
microcontrollers
which,
using
2
-
oo
-
3 hardware
voters,
set
the
outputs
to
the
field.
Any
discrepancy
between
a commanded
output
state
and
the
field
output
is
detected
by
the
microcontrollers
and
reported
to
the
appropriate
MPP
OFFLINE/STARTUP DIAGNOSTICS
When
a SC300E’s
MPPs
are
f
irst
powered
up,
the
following
diagnostic
routines
are
executed:
Initialisation
of
all
SRAM
Memory
configuration
and
size
checks
RTTS
and
application
logic
copied
to
SRAM
All
program
checksums
recalculated
and
checked
Configuration
and
checksums
of
neighbouring
MPPs
read
and
confirmed
Initialisation
of
synchronisation
registers
Synchronisation
registers
of
neighbouring
processors
read
A processor
will
then
pause,
waiting
for
the
other
two
MPPs
to
complete
their
startup
diagnostics.
At
powerup
a SC300E
system
must
have
three
healthy
MPPs,
otherwise
the
startup
diagnostics
will
prevent
execution
of
the
system
application
logic.
In
the
event
of
a processor
failing
a replacement
MPP
can
be
brought
online
using
a warm
start
command.
Warm
start
commands
can
be
issued
from
a TriBuild
workstation
or
by
use
of
an
application
logic
assigned
input.
A newly
installed
MPP
will
execute
its
startup
diagnostics,
monitor
the
running
MPP’s
synchronisation
registers
and
await
a warm
start
command.
At
this
point
checksums
wi
ll
be
confirmed
and
the
new
MPP
acquires
I/O
data
tables
from
its
neighbours
and
commences
execution
of
its
application
logic.
Online/continuous diagnostics
All
memory
reads
and
writes
are
automatically
checked
for
errors
by
the
MPPs'
error
checking
and
correcting
circuitry.
Single
memory
errors
are
detected
and
corrected,
all
multiple
errors
are flagged.
Software
Implemented
Fault
Tolerant
(SIFT)
votes
the
data
tables
between
the
MPPs
using
a
majority
vote
algorithm,
any
errors
being
logged
and
corrected
by
the
processors
during
their
'read
neighbour's
data'
cycle.
Corrected
memory
errors
are
logged
in
diagnostic
history
tables.
These
tables
can
be
accessed
by
application
logic
functions
and
be
used
to
generate
system
alarms.
If
multiple
errors
are
detect
ed
an
MPP
will
be
halted.
An
MPP’s
I/O
hot
repair
task
regularly
scans
all
Przeglądanie stron 11