Rockwell-automation RECOMM-ENET EtherNet/IP Communications Module Instrukcja Użytkownika Strona 141

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 194
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 140
EtherNet I/P Objects
C-5
C.3 Register Object
Class Code
Instances
Class Attributes
Hexadecimal Decimal
0x07 7
Instance Description
1 All I/O data being read from the DPI device (read-only)
2 All I/O data written to the DPI device (read/write)
3 Logic Status and Feedback data (read-only)
4 Logic Command and Reference data (read/write)
5 Datalink A (input data from device to scanner) (read only)
6 Datalink A (output data from scanner to device) (read/write)
7 Datalink B (input data from device to scanner) (read only)
8 Datalink B (output data from scanner to device) (read/write)
9 Datalink C (input data from device to scanner) (read only)
10 Datalink C (output data from scanner to device) (read/write)
11 Datalink D (input data from device to scanner) (read only)
12 Datalink D (output data from scanner to device) (read/write)
13 Logic Status and Feedback Data (read-only)
14
Mask
1
(read/write)
1
The mask command word is set to the value of the first word of the data
where there are ones in the second word of the data. Command = (word
1 and not word 2) or (word 1 and word 2). This only controls specified bits
in the Logic Command data to the DPI product and does not change the
Reference value.
15 Logic Status (read-only)
16 Logic Command (read/write)
17 Feedback (read-only)
18 Reference (read/write)
Attribute
ID
Access
Rule Name Data Type Description
100 Set Control Timeout UINT Control timeout in seconds
Przeglądanie stron 140