Chapter 2 –Installation/Wiring
2-11
POWER WIRING
Input and output power connections are performed through a
ten position terminal block, TB1 (see page 2-3 for location).
Figure 2.6 Power Terminal Block Designations (TB1)
GND GND L1
R
L2
S
L3
T
+DC BRK
(-DC)
T1
U
T2
V
T3
W
Required Branch
Circuit Disconnect
AC Input Line
To Motor
Connection for Dynamic Brake Resistors for all models except the 200-230 Volt,
0.37 to 0.75 kW (1/2 to 1 HP) drive. IMPORTANT: The [DB Enable] parameter must
be enabled for proper operation.
For single phase applications, the AC input line can be connected to any two of
the three input terminals R, S, T (L1, L2, L3).
Bulletin 1305 drives are UL listed and CSA certified as a motor overload protec-
tive device. An external overload relay is not required
for single motor applications.
IMPORTANT: This drive is not intended for use with single phase motors.
Ground from drive to motor frame must be an independent continuous insulated
wire run.
To
Motor
Required
Input Fusing
Table 2.B Power Block Terminal (TB1)
Terminals Description
GND Earth Ground
R, S, T (L1, L2, L3) AC Input Line Terminals
+DC, BRK (or -DC) Dynamic Brake Option - Refer to instructions included
with option
U, V, W (T1, T2, T3) Motor Connection
Table 2.C Screw Size, Wire Size and Torque Specifications
Terminal Screw
Size
Max./Min. Wire Size
mm
2
(AWG )
Maximum Torque
N-m ( lb-ins. )
TB1
(0.37 to 0.75kW/1/2 to 1 HP)
M4 3.5/0.75 (12/18) 0.90 (8)
TB1 (All except above) M4 4/0.75 (10/18) 1.81 (16)
TB2 (All) M3.5 1.5/0.20 (14/24) 0.90 (8)