Chapter 5 –Programming
5-5
Metering
This group of parameters consists of commonly viewed drive operating conditions such as drive output fre-
quency, output voltage, output current and command frequency. All parameters in this group are Read Only.
ut
ut Cu
t]
Parameter # 54 Factory Default None
ut
ut Cu
t]
Parameter Type Read Only Minimum 0.00
This parameter displays the output current present at TB1,
terminals T1, T2 & T3 (U, V & W).
Units .01 Amps Maximum Two Times Drive
Output Current
ut
ut V
t
g
]
Parameter # 1 Factory Default None
ut
ut V
t
g
]
Parameter Type Read Only Minimum 0
This parameter displays the output voltage present at TB1,
terminals T1, T2 & T3 (U, V & W)
Units 1 Volt Maximum Maximum Voltage
ut
ut
w
]
Parameter # 23 Factory Default None
ut
ut
w
]
Parameter Type Read Only Minimum 0
This parameter displays the output power present at TB1,
terminals T1, T2, & T3 (U, V & W).
Units .01 kW Maximum Two Times Rated
Drive Output Power
DC
us V
t
g
]
Parameter # 53 Factory Default None
DC
us V
t
g
]
Parameter Type Read Only Minimum 0.00
This parameter displays the DC bus voltage level. Units 1 Volt Maximum 410 - 230V Drive
815 - 460V Drive