Rockwell-automation 150 USE MN/SMC DIALOG + CONTROLLER Instrukcja Użytkownika Strona 170

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 169
Appendix B
Parameter Information
Table B.1 Parameter List
Read-only capability.
Group
Parameter
Description
Parameter
Number
Display
Units
Scale
Factor
Minimum Maximum
Default
Setting
User
Setting
Metering
Voltage
Phase A–B
1Volts1
Voltage
Phase B–C
2Volts1
Voltage
Phase C–A
3Volts1
Current
Phase A
4Amps10
Current
Phase B
5Amps10
Current
Phase C
6Amps10
Wattmeter 7 kW 10
Kilowatt
Hours
8kWH1
Elapsed
Time
9Hours1
Power
Factor
10 100
Motor Thermal
Usage
11 % 1
Faults
Clear Fault 18 No, Yes No
Fault
Buffer #1
19 1
Fault
Buffer #2
20 1
Fault
Buffer #3
21 1
Fault
Buffer #4
22 1
Fault
Buffer #5
23 1
Basic Setup
SMC Option
14
Standard, Soft Stop, Pump Control, Preset Slow
Speed, Smart Motor Braking, Accu-Stop, or Slow
Speed with Braking
Starting Mode 28 Soft Stop, Current Limit Soft Start
Ramp Time #1 30 Seconds 1 0 30 10
Initial Torque
#1
31 % LRT 1 0 90 70
Current Limit
Level
34 % FLC 1 50 600 50
Kickstart Time 35 Seconds 10 0.0 2.0 0.0 (Off)
Przeglądanie stron 169
1 2 ... 165 166 167 168 169 170 171 172 173 174 175 ... 188 189

Komentarze do niniejszej Instrukcji

Brak uwag