A-4 Specifications
1560E-UM050B-EN-P - June 2013
Table A.4 Cable Quantity and Size
Bulletin Size
Structure
Code
Unit Size
Inches (mm)
Max. No. & Size of
Incoming cables-no bus
Max. No. & Size of
Incoming Cables-w/bus
Max. No. & Size of
Exiting Load Cables
1560E 200/400A 14.60
26 W X 91 H
(660 X 2311)
(1) 500/
(2) 250mcm/phase
(1) 500/
(2) 250mcm/phase
(1) 500/
(2) 250mcm/phase
1560E 200/400A 14.62
36 W X 91 H
(914 X 2311)
(1) 500/
(2) 250mcm/phase
(1) 500/
(2) 250mcm/phase
(1) 500/
(2) 350mcm/phase
1560E 600A 14.64
44 W X 91 H
(1118 X 2311)
(1) 500/
(2) 250mcm/phase
(1) 500/
(2) 250mcm/phase
(1) 500/
(2) 350mcm/phase
1562E 200/400A 14.70
36 W X 91 H
(914 X 2311)
(1) 500/
(2) 250mcm/phase
(1) 750/
(2) 500mcm/phase
(1) 500/
(2) 350mcm/phase
1562E 200/400A 14.72
62 W X 91 H
(1575 X 2311)
(1) 500/
(2) 250mcm/phase
(1) 500/
(2) 250mcm/phase
(1) 500/
(2) 250mcm/phase
1562E 600A 14.74
80 W X 91 H
(2032 X 2311)
(1) 750mcm/phase
(1) 750/
(2) 500mcm/phase
(1) 500/
(2) 350mcm/phase
1562E 600A 14.76
100 W X 91 H
(2540 X 2311)
(1) 750mcm/phase
(1) 750/
(2) 500mcm/phase
(1) 1000/ (2) 750/
(4) 500mcm/phase
Notes:
1. Restrictions based upon single conductor cable.
2. Please contact factory for multiple conductors, shielded, or other specialized cables.
3. Please contact factory if the maximum number/size needs to be exceeded. We can accommodate special requests by
incorporating landing pads (if room is available) or cable terminating units.
4. The customer is responsible to size the cables and conduits in accordance with applicable installation codes.