Appendix B
Parameter Information
1560E-UM050B-EN-P - June 2013
Table B.1 – Parameter List
Group Parameter Description
Parameter
Number
Units Min / Max
Default
Settings
User
Settings
Volts Phase A-B 1 V
Volts Phase B-C 2 V
Volts Phase C-A 3 V
Current Phase A 4 A
Current Phase B 5 A
Current Phase C 6 A
Watt Meter 7 KW/MW
Kilowatt Hours 8 KWH/MWH
Elapsed Time 9 Hours
Meter Reset 10
Ready
ETM Reset
KWH Reset
Ready
Power Factor 11 0.00…0.99
Mtr Therm Usage 12 % 0…100
Metering
Motor Speed 13 % 0…100
SMC Option 14
Standard
Brake
Pump Control
Motor Connection 15 Line/Delta Line
Line Voltage 16 V 0…10000 480
Starting Mode 17
Full Voltage
Current Limit
Soft Start Linear Speed
Pump Start
Soft Start
Ramp Time 18 SEC 0…30 10
Initial Torque 19 % LRT 0…90 70
Cur Limit Level 20 % FLC 50…600 350
Torque Limit 21 % LRT 0…100 90
Kickstart Time 22 SEC 0.0…2.0 0.0
Kickstart Level 23 % LRT 0…90 0
Basic Set Up
Option 2 Input Ê 24
Disable
Dual Ramp
Preset SS
Emergency Run
Disable
Starting Mode 2 25
Full Voltage
Current Limit
Soft Start
Linear Speed
Soft Start
Ramp Time 2 26 SEC 0…30 10
Initial Torque 2 27 % LRT 0…90 70
Cur Limit Level 2 28 % FLC 50…600 350
Torque Limit 2 29 % LRT 0…100 90
Kickstart Time 2 30 SEC 0.0…2.0 0.0
Dual Ramp
Kickstart Level2 31 % LRT 0…90 0
Ê Pump modules do not display this parameter. Default setting for MV applications is ‘Emergency Run’.