Chapter 5 Calibrate Your Modules
If at least one channel has been selected and there is a mismatch between
the device in the RSLogix 5000 I/O Configuration and the actual physical
device, another warning dialog comes up. It informs you that this is
dangerous with an active system and there is a mismatch. This message box
gives you an option to quit. Help is provided to you more information.
8. From the Danger dialog, for a module not currently used for control, click
OK to continue.
The Output Calibration - Low Value dialog appears.
9. Record the results of your measurement.
10. Click Next. The Output Calibration - High Value dialog appears.
11. Record the results of your measurement.
12. Click Next to calibrate the module.
The Output Calibration Results page appears.