Rockwell-automation 1732E-OF4M12R ArmorBlock Dual-Port EtherNet/IP 4-P Instrukcja Użytkownika Strona 78

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 96
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 77
70 Rockwell Automation Publication 1732E-UM005A-EN-E - July 2012
Appendix A Specifications
Output Specifications
The 1732E-OF4M12R module has the following input specifications.
Input range
Current input
Voltage input
32 mA, 275 mW
±30V, 20 mA, 25 mW
Input impedance 125 kΩ per channel
Accuracy 0.1% Full Scale @ 25 °C (77 °F)
Accuracy drift with
temperature, max
40 ppm % Full Scale /°C @ 25 °C (77 °F)
Calibration Factory calibrated. Calibration is also supported through
RSLogix 5000.
Overload support
Current input
Voltage input
32 mA
30V continuous
Input Specifications – 1732E-IF4M12R
Attributes Value
Output Specifications – 1732E-OF4M12R
Attributes Value
Number of outputs 4
Resolution, min 16 bits
Data format 16-bit sign magnitude
Conversion rate <
2 ms
Output type Configurable as voltage or current per channel
Output range
Current output
Voltage output
0…20 mA, 4…20 mA
+/-10V, 10 mW
Short circuit protection, max
Current output
Voltage output
20 mA (0…20 mA mode)
20 mA per channel
Accuracy 0.1% Full Scale @ 25 °C (77 °F)
Accuracy drift with
temperature, max
40 ppm % Full Scale /°C @ 25 °C (77 °F)
Calibration Factory calibrated. Calibration is also supported through
RSLogix 5000.
Przeglądanie stron 77
1 2 ... 73 74 75 76 77 78 79 80 81 82 83 ... 95 96

Komentarze do niniejszej Instrukcji

Brak uwag