Publication 1734-UM004F-EN-E - December 2012
26 Configure Your Module
Level alarms - low-low, low, high, and high-high - any value from
-32,768...+32,767 can be entered.
Scaling - Values returned when input is at low scale value or high scale
value. The low and high scale points are different for each sensor input:
Thermocouple Scaling limits
To configure your module, select Configuration as shown in the figure.
Configure a module
Use the procedures in the figures that show basic setup and advanced setup,
noting that you complete steps 1-5 during basic setup, then continue with steps
6-10 during advanced setup.
Thermocouple
Type
Low Scaling
Endpoint
High Scaling
Endpoint
mV 0 mV 70 mV
Type B 212 °F (100 °C) 1832 °F (1000 °C)
Type C 32 °F (0 °C) 4199 °F (2315 °C)
Type E 32 °F (0 °C) 1832 °F (1000 °C)
Type J 32 °F (0 °C) 1832 °F (1000 °C)
Type K 32 °F (0 °C) 1832 °F (1000 °C)
Type N 32 °F (0 °C) 1832 °F (1000 °C)
Type R 32 °F (0 °C) 1832 °F (1000 °C)
Type S 32 °F (0 °C) 1832 °F (1000 °C)
Type T 32 °F (0 °C) 212 °F (100 °C)
To configure your module,
select Configuration and
modify the parameters as
desired for your application.
When complete, download to
your module by clicking the
Download to Device button.
You can download each
change as you make it using
“Single,” or download all your
changes using “All.” If you
press the “Apply” button, only
the selected parameter is
downloaded to the module.
Click here when finished.