Publication 1734-UM004F-EN-E - December 2012
32 Configure Your Module
Advanced Setup Parameters
Advanced parameters you can set for the RTD module consist of:
Notch filter – Select the Notch Filter for the analog to digital converter.
At higher frequencies, faster sample rates are possible
50 Hz
60 Hz (default)
100 Hz
120 Hz
200 Hz
240 Hz
300 Hz
400 Hz
480 Hz
If the filter value is changed, the module may require calibration to meet
specifications.
Digital filter – A digital filter is available on this module. You set a time
constant that is used in the equation:
Yn = Yn-1 + (dt / (dt + T
A
) * (Xn-Yn-1)
Where: Yn = new data
Yn-1 = old data
dt = Channel Update Rate in milliseconds
T
A
= digital filter time constant
Xn = present unfiltered data
T
A
can be an integer from 0 to 10,000 ms. If set to 0, the filter is
disabled.
Enable alarms latch – If enabled, alarms for this channel latch
FAULTED until a Latch Reset command is received.
The alarms effected are:
Input Status
Low and High level
Range
Disable alarms – If Alarms are Disabled, all alarms for this channel
show No FAULT. This is useful for unused channels.
Level alarms – low-low, low, high, and high-high.