Rockwell-automation 1746-NI8 SLC 500 Analog Input Modules User Manual Instrukcja Użytkownika Strona 16

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 15
2–2
Quick Start
Publication
17466.8 - April 1997
1.
Check the contents of shipping box.
Reference
Unpack the shipping box making sure that the contents include:
analog input module (Catalog Number 1746NI8)
removable terminal block (factoryinstalled)
If the contents are incomplete, call your local AllenBradley representative for assistance.
-
2.
Ensure that your chassis and power supply support the 1746NI8
module.
Reference
Review the power requirements of your system to see that your chassis supports the module:
If combining a 1746NI8 module with another I/O module in a fixed controller, refer to the I/O
module compatibility table found in chapter 3.
For modular style systems, calculate the total load on the system power supply using the
procedure described in the SLC Installation & Operation Manual for Modular Style Controllers
(publication 17476.2) or the SLC 500 Family System Overview (publication 17472.30).
The 1746NI8 backplane current consumption is 200 mA at 5V dc and 100 mA at 24V dc.
Chapter 3
(Installation and
Wiring)
Appendix A
(Specifications)
3.
Select voltage or current input type to match the analog sensor.
Reference
The voltage/current selection DIP switches are located on the side of the module. The switch
settings are
OFF = VOLTAGE INPUT and ON = CURRENT INPUT.
Chapter 3
(Installation and
Wiring)
O
21
N
O
21
N
O
21
N
O
21
N
VOLTAGE
CURRENT
CH7CH0
Procedures
Przeglądanie stron 15
1 2 ... 11 12 13 14 15 16 17 18 19 20 21 ... 90 91

Komentarze do niniejszej Instrukcji