Rockwell-automation 1746-NI8 SLC 500 Analog Input Modules User Manual Instrukcja Użytkownika Strona 28

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 27
3–7
Installation and Wiring
Publication
17466.8 - April 1997
Wiring SingleEnded and Differential Inputs
The diagram below shows typical wiring for the module.
shield
shield
shield
shield
shield
shield
shield
shield
singleend
signal source
singleend
signal source
singleend
signal source
singleend
signal source
differential
signal source
differential
signal source
differential
signal source
differential
signal source
+
+
+
+
+
+
+
+
Shield
Channel 0
Channel 2
Channel 1
Channel 3
Channel 4
Channel 5
Channel 6
Channel 7
Shield
Important: Follow these guidelines when wiring the module.
Use shielded communication cable (Belden 8761) and keep length as short as possible.
Connect only one end of the cable shield to earth ground.
Connect the shield drain wires for channels 0-3 to the top shield terminal.
Connect the shield drain wires for channels 4-7 to the bottom shield terminal.
Shield terminals are internally connected to chassis ground which is connected to earth ground via the SLC backplane.
Singleended source commons may be jumpered together at the terminal block.
Channels are not isolated from each other.
If a differential signal source has an analog common, it can not and must not be connected to the module.
Common mode voltage range is $10.5 volts. The voltage between any two terminals must be less than 21 volts.
The module does not provide power for the analog inputs.
Use a power supply that matches the transmitter (sensor) specifications.
+
+
+
+
+
+
+
+
+
+
+
+
+
Power
Supply
Connections
Przeglądanie stron 27
1 2 ... 23 24 25 26 27 28 29 30 31 32 33 ... 90 91

Komentarze do niniejszej Instrukcji

Brak uwag