Appendix
B
Publication
17466.8 - April 1997
Configuration Worksheet
The following worksheet is provided to help you configure each of
the channels on your module. See Chapter 5 for detailed
configuration information.
• Input Type
• Data Format
• Open Circuit
• Filter Frequency
• Channel Enable
• Not Used
Channel 0
Channel 1
Channel 2
Channel 3
1112131415
0000
910 8 67450123
0000
0000
0000
Bit Number
Channel 4
Channel 5
Channel 6
Channel 7
0000
0000
0000
0000
Bit
Definitions:
Bits 0-2
Input Type
000 = ±10V dc
001 = 1-5V dc
010 = 0-5V dc
011 = 0-10V dc
100 = 0-20 mA
101 = 4-20 mA
110 = ±20 mA
111 = 0-1 mA
Bits 3- 5 Data Format
000 = engineering units
001 = scaledforPID
010 = proportional counts
011 = 1746NI4 data format
100 = user defined scaling
101 = user defined scaling
110 = illegal
111 = illegal
Bits 6 and 7 Open Circuit 00 = zero 01 = upscale 10 = downscale 11 = illegal
Bits 8-10 Filter Frequency
000 = no filter
001 = 75 Hz
010 = 50 Hz
011 = 20 Hz
100 = 10 Hz
101 = 5 Hz
110 = 2 Hz
111 = 1 Hz
Bit 11 Channel Enable 0 = channel disabled 1 = channel enabled
Bits 12-15 Not Used 0000 = always make this setting