Rockwell-automation 1757-FFLD Linking Device Configuration Manual Instrukcja Użytkownika Strona 105

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 104
Publication 1757-PM002A-EN-E - June 2006
Applications 4-51
Split Range PID Logic
Block Block Type Parameter Element Value
PRESSURE Analog Input MODE_BLK TARGET Auto
XD_SCALE * EU_100
EU_0
UNITS_DECIMAL
DECIMAL
CHANNEL 1
L_TYPE Direct
PID PID MODE_BLK TARGET CAS
GAIN Loop
Dependent
RESET
RATE
PV_SCALE (these
values must
match in Analog
Input range)
EU_100
EU_0
UNITS_DECIMAL
DECIMAL
SPLIT Splitter MODE_BLK TARGET CAS
IN_ARRAY ** 0,48,50,100
OUT_ARRAY ** 100,0,0,100
VENT Analog Output MODE_BLK TARGET CAS
XD_SCALE * EU_100
EU_0
UNITS_DECIMAL
DECIMAL
CHANNEL 1
L_TYPE Direct
N2 Analog Input MODE_BLK TARGET CAS
XD_SCALE * EU_100
EU_0
UNITS_DECIMAL
DECIMAL
CHANNEL 1
L_TYPE Direct
Przeglądanie stron 104
1 2 ... 100 101 102 103 104 105 106 107 108 109 110 ... 149 150

Komentarze do niniejszej Instrukcji

Brak uwag