4-28 Applications
Edit the PID Regulatory Routine
1. Double-click Pressure Loop.
A blank sheet opens.
2. Enter >PIC101< in the name box.
3. On the Process Tab, click PIDE (Enhanced PID Block).
The block is added to the sheet.
4. Click the Block Properties button .
The PIDE Properties window opens.
The first column distinguishes between
Input (I) and Output (O) parameters.
The checkmarks in the Vis column show that a parameter
is selected and therefore visible on the block.