Bad Network Scope Display
Bad network signals can inhibit the performance of your network. A common
reason for bad signals is the addition of one or more unnecessary terminators
in a network.
Figure 2.12 shows a bad signal due to only one terminator in a system, while
Figure 2.13 shows a bad signal due to one extra terminator (3 total).
Figure 2.12 Bad Network Signal Due to One Terminator
(1)
WA
R
Remember, there can be only two terminators per bus segment.
(1)
11.4.3 FF Engineering Guide