3-6 Configuring the Module
3. Click on the Chan. 1 tab (Figure 3.3) and set the I/O Config data
area accordingly. In this example, the 1769-SM2 is configured to
fault if the controller is switched to Program mode, and one drive is
connected at node address 100.
Figure 3.3 Chan. 1 Tab Data Example Screen
Important: When using Multi-Drive mode, the node addresses
entered in the Drive Addr x fields must match the
corresponding drive Parameter 104 - [Comm Node
Addr] value in the PowerFlex 4-Class drives so that the
1769-SM2 module will communicate with the drives.
Note that the DSI Fault Config settings can only be accessed if the
Idle Action is set to “Send Flt Cfg” (Figure 3.4
).