10–3Diagnostic Status Information
Publication
17706.5.16 - October 1996
1747L20, L30, L40, L511, L514, L524 (SLC 500, SLC 5/01 and
SLC 5/02 processors) Status Bytes
Bytes Bits Contents Description
1 07 mode/status 00
2 07 type extender EE
3 07 extended interface type 1F
4 07 extended processor type 1A = 20, 30, & 40 I/O SLC fixed controllers
18 = 1747L511, L514 SLC 5/01 controller
25 = 1747L524 and SLC 5/02 controller
5
04
series/revision
= 0 (firmware release1)
= 1 (firmware release 2), etc.
57 = 0 (series A)
= 1 (series B), etc.
6 - 16 all bulletin number/name
(in ASCII)
500 - 20 = 1747L20 (SLC 500 fixed controller)
500 - 30 = 1747L30 (SLC 500 fixed controller)
500 - 40 = 1747L40 (SLC 500 fixed controller)
5/01 = 1747L511 & L514
5/02 = 1747L524
Productspecific Information
17 all major error word low byte
18 all major error word high byte
19
04
processor mode
status/control word
0 = download 1 = program
2 = reserved 3 = idle due to SUS instruction
4 = reserved 5 = reserved
6 = run 7 = test continuous scan
8 = test single scan 931 = reserved
5 forces active
6 forces installed
7 communication active
20
0
processor mode status/control word
protection power loss
1
(high byte)
startup protect fault
➀
2
load memory module on error
3
load memory module always
➀
4
load memory module and run
➀
5 major error processor halted
6
locked
➀
7
first pass bit
➀
21 07
program ID
low byte
22 07
high byte
23 07 processor RAM size (in Kbytes)
24
0 directory file corrupted
1 not used = 0
27 program owner node address = 00 - 1F: program owner node address
= 3F: no program owner
➀
SLC 5/02 processors only.