Przeglądanie stron 176
10–6 Diagnostic Status Information
Publication
17706.5.16 - October 1996
1761L16AWA, L16BBB, L16BWB, L32AWA, L32BWA,
L32BWB (MicroLogix 1000 processors) Status Bytes
Bytes Bits Contents Description
1 07 mode/status 00
2 07 type extender EE
3 07 extended interface type 34 = DF1 fullduplex protocol on port 0
20 = DH485
4 07 extended processor type 58
5
04
series/revision
= 0 firmware release1
= 1 firmware release 2, etc.
57 = 0 series A
= 1 series B, etc.
6 - 16 all bulletin number/name
(in ASCII)
Productspecific Information
17 all major error word low byte
18 all major error word high byte
19
04
processor mode
status/control word
00000 = download
00001 = remote PROG
00011 = idle due to SUS instruction
00110 = RUN
00111 = TEST; continuous scan
01000 = TEST; single scan
5 forces active
6 forces installed
7 communication active
20
0
processor mode status/control
fault override
1
p
word (high byte)
startup protect fault
2 reserved
3 reserved
4 always run
5 major error  processor halted
6 locked
7 first pass bit
21 07
program ID
low byte
22 07
pg
high byte
23 07 processor RAM size (in Kbytes) 8
24
0 directory file corrupted
1 not used = 0
27 program owner node address = 3F; no program owner