ControlNet Modular Repeater Adapter 19
Rockwell Automation Publication 1786-IN013F-EN-P - April 2011
Specifications
Technical Specifications - 1786-RPA/B
Attribute 1786-RPA/B
Power consumption, max 16.8 W
Power dissipation, max 8.8 W
Input voltage rating, max 700 mA @ 24V DC, Class 2/SELV
(1)
(1) For applications within the U.S., use a power supply that is appropriately certified as Class 2 per the
definition in the National Electrical Code, ANSI/NFPA 70, Article 725. For applications outside the
U.S., use a power supply with safety extra low voltage (SELV) or protected extra low voltage (PELV)
output. A power supply with SELV or PELV output is built with appropriate isolation to withstand single
fault conditions. The output cannot exceed 30V rms, 42.4V peak, or 60V DC under fault conditions.
Input voltage range 18…36V DC
Backplane output current, max 1.6A @ 5V DC
Minimum enclosure size (HxWxD), approx 304.8 x 196.8 x 101.6 mm
(12 x 7.75 x 4 in.)
Mounting orientation Any mounting orientation
Isolation voltage 50V (continuous), Basic insulation type,
Power to system
Type tested at 710V DC for 60 s
Wire size 0.21…3.3 mm
2
(24...12 AWG) solid or
stranded copper wire rated at 75 °C
(167 °F ), or greater, 1.2 mm (3/64 in.)
insulation max for power connections
Wiring category 2 - on power ports
2 - on communication ports
(2)
(2) Use this Conductor Category information for planning conductor routing. Refer to Industrial
Automation Wiring and Grounding Guidelines, publication 1770-4.1
.
Enclosure type rating None (open-style)
North American temp code T5
IEC temp code T4