Rockwell Automation Publication 1788-UM059A-EN-P - August 2014 11
Install the Linking Device Chapter 2
2. Connect the power cable to the linking device.
The female terminal block connector is provided with the linking device.
3. Apply power to the linking device and DeviceNet network.
Set the DeviceNet Node
Address and Data Rate
Two methods can be used to set the DeviceNet node address and the data rate:
• Use the node address and data rate rotary switches on the side of the
linking device
• Use RSNetWorx for DeviceNet software
Set the DeviceNet Node Address and Data Rate by Using the
Rotary Switches
The rotary switches are on the right side of the linking device.
Set the desired node address and data rate according to the table below.
Pin No. Description
1 +24 V DC
2GND
3PE (Protective Earth)
Switch Node Address
00 - 63 DeviceNet node address
Other value Node address selected via RSNetWorx
software
Switch Data Rate
0 125 kbps