Rockwell-automation 25-COMM-E2P PowerFlex 25-COMM-E2P Dual-Port EtherN Instrukcja Użytkownika Strona 141

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 140
Rockwell Automation Publication 520COM-UM003A-EN-E - June 2013 141
EtherNet/IP Objects Appendix C
N41:0
N41:1
N41:2
N41:3
N41:4
N41:5
N41:6
N41:7
N41:8
N41:9
N41:10
Logic Command Word
Unused
Reference
Unused
Datalink From Net 1
Unused
Datalink From Net 2
Unused
Datalink From Net 3
Unused
Datalink From Net 4
Logic Status Word
Unused
Feedback
Unused
Datalink To Net 1
Unused
Datalink To Net 2
Unused
Datalink To Net 3
Unused
Datalink To Net 4
N42 This N-file lets you read and write some values configuring the port
N42:3 Time-out (read/write): Time (in seconds) allowed between messages to the N41 or N44 file. If the
adapter does not receive a message in the specified time, it performs the fault action configured in
parameter C143 [EN Comm Flt Action].
N42:7 Adapter Port Number (read only): DPI port on the drive to which the adapter is connected.
42:8 Peer Adapters (read only): Bit field of devices having DPI Peer capabilities.
N44 For Multi-drive mode Only
This N-file lets you read and write control I/O messages. You can write control I/O messages only when
all of the following conditions are true:
The adapter is not receiving I/O from a scanner. For example, there is no scanner on the network,
the scanner is in idle (program) mode, the scanner is faulted, or the adapter is not mapped to the
scanner.
The value of N42:3 is set to a non-zero value.
Write Read
N44:0
N44:1
N44:2
N44:3
N44:4
N44:5
N44:6
N44:7
N44:8
N44:9
N44:10
Drive 0 Logic Command
Unused
Drive 0 Reference
Drive 1 Logic Command
Drive 0 Reference
Drive 2 Logic Command
Drive 2 Reference
Drive 3 Logic Command
Drive 3 Reference
Drive 4 Logic Command
Drive 4 Reference
Drive 0 Logic Status
Unused
Drive 0 Feedback
Drive 1 Logic Status
Drive 1 Feedback
Drive 2 Logic Status
Drive 2 Feedback
Drive 3 Logic Status
Drive 3 Feedback
Drive 4 Logic Status
Drive 4 Feedback
N10...N18 These N-files lets you read and write parameter values in the drive and the adapter.
Single-Drive Mode Multi-Drive Mode
N10:0
N10:1...999
Number of parameters in the drive
Drive parameters 1...999
Number of parameters in Drive 0
Drive 0 parameters 1...999
N11:0...999 Drive parameters 1000...1999 Drive 0 parameters 1000...1999
N12:0...999 Drive parameters 2000...2999 Drive 0 parameters 2000...2999
N13:0 Number of parameters in this adapter Number of parameters in this adapter
N13:1...999 Parameters 1...999 in this adapter Parameters 1...999 in this adapter
N14:0 Number of parameters in the DSI device Number of parameters in Drive 1
N14:1...999 Parameters 1...999 in the DSI device Drive 1 parameters 1...999
N15:0 Number of parameters in this adapter Number of parameters in Drive 2
N15:1...999 Parameters 1...999 in this adapter Drive 2 parameters 1...999
N16:0 Not supported Number of parameters in Drive 3
N16:1...999 Not supported Drive 3 parameters 1...999
N17:0 Not supported Number of parameters in Drive 4
N17:1...999 Not supported Drive 4 parameters 1...999
N18:0 Not supported Number of parameters in this adapter
N18:1...999 Not supported Parameters 1...999 in this adapter
N-File Description
Przeglądanie stron 140
1 2 ... 136 137 138 139 140 141 142 143 144 145 146 ... 171 172

Komentarze do niniejszej Instrukcji