Rockwell Automation Publication 520COM-UM003A-EN-E - June 2013 59
Configuring the I/O Chapter 4
Generic Profile Example of I/O Image
For the example below, all four [Opt Data In x] and all four [Opt Data
Out x] parameters are used, resulting in an Input Size of “8” and an
Output Size of “6.”
5. After setting the information in the drive’s New Module window, click
OK. The Module Properties window appears.
The Host Datalink parameters [Opt Data In x] and [Opt Data Out x] do
not actually contain data. These are user-configurable parameters that
only contain the parameter number of the parameter whose data will
be made available for write/read in the I/O image. See Using Datalinks
on page 66.
Adapter
Word and I/O
Logic CommandWord 0
ReferenceWord 1
Datalink 1Word 2
Datalink 2Word 3
Datalink 3Word 4
Datalink 4Word 5
Logic StatusWord 2
FeedbackWord 3
Required
Padword
(1)
Word 0
PadwordWord 1
Datalink 1Word 4
Datalink 2Word 5
Datalink 3Word 6
Datalink 4Word 7
Optional
Required
Optional
Output
Image
(Write)
Input
Image
(Read)
(1) Padwords only apply when using the generic profile. Padwords are not used when using the full-featured drive Add-
On-Profile.