This chapter describes network and device connections for PanelView
terminals.
Wiring and safety guidelines
Cable charts
Remote I/O connections
DH+ connections
DH-485 connections
RS-232 (DH-485) connections
RS-232 (DF1) connections
ControlNet connections
DeviceNet connections
EtherNet/IP connections
PanelView 300 Micro connections
Computer or printer connection to RS-232 serial port
Wiring and Safety
Guidelines
Use publication NFPA 70E, Electrical Safety Requirements for
Employee Workplaces when wiring the PanelView terminals. In
addition to the NFPA general guidelines:
route communication cables to terminal by a separate path from
incoming power.
where power and communication lines must cross, they should
cross at right angles. Communication lines can be installed in the
same conduit as low level dc I/O lines (less than 10 volts).
grounding minimizes noise from Electromagnetic Interference
(EMI) and is a safety measure in electrical installations.
use the National Electric Code published by the National Fire
Protection Association as a source for grounding.
IMPORTANT
Do not run signal wiring and power wiring in the
same conduit.