Rockwell-automation 2711 Standard PanelView Operator Terminal User Man Instrukcja Użytkownika Strona 258

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 257
258 Publication 2711-UM014G-EN-P - September 2008
Appendix B Messages, Codes and Self-test Numbers
DF1 Terminal Messages
Terminal Codes
Terminal Codes are displayed on the PanelView terminal during
operation or terminal configuration.
DeviceNet Codes
Comm Status codes appear as a banner at the top of an application
screen or as a status indicator on the terminal’s Configuration screen.
Error 634 appears in upper left of banner. Codes less than 12 are
minor faults and clear automatically when corrected. Codes above 12
require a terminal reset to clear.
Error Number Terminal
Messages
Type Meaning Recommended Action
675 or 682 Required network
node(s) not found
Comm Status The network is active, but the logic
controller(s) are not located at the
expected nodes.
Verify that the logic controller(s)
required by the application are at the
expected node addresses and that
the communication parameters are
set properly.
676 or 683 File access error Comm Status The terminal is trying to access one
or more controller data files that are
unavailable. If the message is
flashing, the terminal is trying to read
or write data files that are
unavailable.
The data files do not exist on the
controller. Create the data files.
679 or 686 Panelview offline Comm Warning PanelView is offline. Check connections
681 or 688 DF1 hardware
failed
Comm Status During startup the terminal detected
a missing, corrupt, or nonfunctional
DF1+ card. The terminal will run but
not communicate.
Contact technical support and provide
terminal message.