Rockwell-automation 2711 Standard PanelView Operator Terminal User Man Instrukcja Użytkownika Strona 213

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 212
Publication 2711-UM014G-EN-P - September 2008 213
Terminal Connections Chapter 12
Making DeviceNet Connections
Use one of the cables below to connect the DeviceNet version of the
PanelView terminal to a DeviceNet network.
Cable Publication No.
DeviceNet Cable, 50 m (164 ft) 1485C-P1A50
DeviceNet Cable, 100 m (328 ft) 1485C-P1A150
DeviceNet Cable, 150 m (492 ft) 1485C-P1A300
IMPORTANT
Refer to DeviceNet Cable System Planning and Installation
manual, publication DNET-UM072
for network layout and
design information
DeviceNet
Terminal Block
Terminal Signal Function Color
1 COM Common Black
2 CAN_L Signal Low Blue
3 SHIELD Shield Uninsulated
4 CAN_H Signal High White
5 V DC+ Power Supply Red
1
5
Przeglądanie stron 212
1 2 ... 208 209 210 211 212 213 214 215 216 217 218 ... 291 292

Komentarze do niniejszej Instrukcji

Brak uwag