5-10 Communications Data for Modbus
The parameter will not be shown on the Controller display when Alarm 3 is not assigned to an output.
Table 5.9
Address Parameter Name Setting (Monitor) Value Function
Group
Four-byte
mode
Two-byte
mode
0F0E 2F07 Alarm 3 Latch H'00000000 (0): OFF
H'00000001 (1): ON
Advanced
Setting
0F10 2F08 Alarm 3 Hysteresis H'00000001…H'0000270F
(0.1…999.9 for TC/Pt multi-input models)
(0.01…99.99 for Analog input models)
Initial
Setting
0F18 2F0C Standby Sequence Reset H'00000000 (0): Condition A
H'00000001 (1): Condition B
Advanced
Setting
0F1A 2F0D Auxiliary Output 1 Open in Alarm H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
0F1C 2F0E Auxiliary Output 2 Open in Alarm H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
0F1E 2F0F Auxiliary Output 3 Open in Alarm H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
0F22 2F11 Alarm 1 ON Delay H'00000000…H'000003E7 (0…999)
0F24 2F12 Alarm 2 ON Delay H'00000000…H'000003E7 (0…999)
0F26 2F13 Alarm 3 ON Delay H'00000000…H'000003E7 (0…999)
0F2A 2F15 Alarm 1 OFF Delay H'00000000…H'000003E7 (0…999)
0F2C 2F16 Alarm 2 OFF Delay H'00000000…H'000003E7 (0…999)
0F2E 2F17 Alarm 3 OFF Delay H'00000000…H'000003E7 (0…999)
1000 3000 PV/SP Display Screen Selection H'00000000 (0): PV/SP
H'00000001 (1): PV/SP/multi-SP
PV/SP/MV
H'00000002 (2): PV/SP/MV
PV/SP/multi-SP
H'00000003 (3): PV/SP/multi-SP
H'00000004 (4): PV/SP/MV
H'00000005 (5): PV/SP/multi-SP
PV/SP/soak time remain
H'00000006 (6): PV/SP/MV
PV/SP/soak time remain
H'00000007 (7): PV/SP/soak time remain
1002 3001 MV Display Selection H'00000000 (0): MV (heating)
H'00000001 (1): MV (cooling)
1006 3003 Automatic Display Return Time H'00000000 (0): OFF
H'00000001…00000063 (1…99)
1008 3004 Display Refresh Period H'00000000 (0):OFF
H'00000001 (1): 0.25
H'00000002 (2): 0.5
H'00000003 (3): 1.0
1010 3008 Additional PV Display H'00000000 (0): OFF
H'00000001 (1): ON
1016 300B MV Display H'00000000 (0): OFF (display of manipulated variable OFF)
H'00000001 (1): ON (display of manipulated variable ON)
1018 300C Protect Function Group Move time H'00000001…H'0000001E (1…30)