SA3100 Drive Configuration and Programming
Power Device Status Register (Continued) 204/1204
Phase V-Upper IOC A Bit 1
The Phase V-Upper IOC A bit is set if an
overcurrent is detected in the phase V upper
power device.
Hex Value: 0002H
Sug. Var. Name: V_UPA@
Access: Read only
UDC Error Code: N/A
LED: N/A
Phase W-Upper IOC A Bit 2
The Phase W-Upper IOC A bit is set if an
overcurrent is detected in the phase W
upper power device.
Hex Value: 0004H
Sug. Var. Name: W_UPA@
Access: Read only
UDC Error Code: N/A
LED: N/A
Phase U-Lower IOC A Bit 3
The Phase U-Lower IOC A bit is set if an
overcurrent is detected in the phase U lower
power device.
Hex Value: 0008H
Sug. Var. Name: U_LOA@
Access: Read only
UDC Error Code: N/A
LED: N/A
Phase V-Lower IOC A Bit 4
The Phase V-Lower IOC A bit is set if an
overcurrent is detected in the phase V lower
power device.
Hex Value: 0010H
Sug. Var. Name: V_LOA@
Access: Read only
UDC Error Code: N/A
LED: N/A
Phase W-Lower IOC A Bit 5
The Phase W-Lower IOC bit is set if an
overcurrent is detected in the phase W
lower power device.
Hex Value: 0020H
Sug. Var. Name: W_LOA@
Access: Read only
UDC Error Code: N/A
LED: N/A