Rockwell-automation SB3000 Configuration and Programming Instrukcja Użytkownika Strona 34

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 122
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 33
3-16
SB3000 Drive Configuration and Programming
UDC Module Fiber-Optic Link Status Register 88/1088
This register shows the current operating state of the fiber-optic link
to the PMI. The lower byte (bits 0-7) shows the actual link status
while the upper byte (bits 8-15) shows whether the communication
taking place is synchronized or not.
Sug. Var. Name: N/A
Units: N/A
Range: N/A
Access: Read only
If the lower byte is equal to:
xx01H:the UDC module is waiting for a request from the PMI for an operating system.
xx02H:the UDC module is downloading an operating system to the PMI.
xx03H:the UDC module and the PMI are exchanging data.
xx06H:the external loopback test is being conducted on the fiber-optic link.
If the upper byte is equal to:
01xxH:the communication between the UDC module and the PMI is synchronized.
02xxH:the communication between the UDC module and the PMI is not synchronized.
UDC Module Transmitted Message Count Register 89/1089
This register contains the number of messages transmitted by the
UDC module.
Sug. Var. Name: N/A
Units: Counts
Range: N/A
Access: Read only
Przeglądanie stron 33
1 2 ... 29 30 31 32 33 34 35 36 37 38 39 ... 121 122

Komentarze do niniejszej Instrukcji

Brak uwag