3-36
SB3000 Drive Configuration and Programming
Power Device Status Register (Continued) 204/1204
Phase W Loss Bit 11
The Phase W Loss bit is set if AC line phase
W is lost.
Hex Value: 0400H
Sug. Var. Name: W_PL@
Access: Read only
UDC Error Code: N/A
LED: N/A
Over Temperature A Bit 12
The Over Temperature A bit is set if an over
temperature fault or warning occurs in
Power Module A.
Hex Value: 1000H
Sug. Var. Name: OTA@
Access: Read only
UDC Error Code: N/A
LED: N/A
Phase U Current Sharing A Bit 13
The Phase U Current Sharing A bit is set if
Power Module A is not carrying its share of
the phase U current.
Hex Value: 2000H
Sug. Var. Name: U_SHRA@
Access: Read only
UDC Error Code: N/A
LED: N/A
Phase V Current Sharing A Bit 14
The Phase V Current Sharing A bit is set if
Power Module A is not carrying its share of
the phase V current.
Hex Value: 4000H
Sug. Var. Name: V_SHRA@
Access: Read only
UDC Error Code: N/A
LED: N/A
Phase W Current Sharing A Bit 15
The Phase W Current Sharing A bit is set if
Power Module A is not carrying its share of
the phase W current.
Hex Value: 8000H
Sug. Var. Name: W_SHRA@
Access: Read only
UDC Error Code: N/A
LED: N/A