Rockwell-automation 1747-DTAM-E,D17476.1 Data Table Access Module (DTA Instrukcja Użytkownika Strona 92

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 91
9-12 Troubleshooting
Publication 1747-6.1
PROCESSOR ERRORS
Error
Code
Module Display Fault Description
0016 START AFTER P.F.
Startup protection after power loss. Error
condition exists at powerup when bit S:1/9 is
set and powerdown occurred while running.
0017
1
1. Error codes for 5/03 processor only
PRC/MMOD MISMATCH NVRAM/memory module mismatch.
001F
1
BAD ONLINE EDIT
A program integrity problem occurred during
an online editing session.
0020 MINOR ERR AT END A minor error bit is set at the end of the scan.
0021 REM. POWER FAIL
A remote power failure of an expansion I/O
rack has occurred.
0022 WATCHDOG TIMEOUT
The user watchdog scan time has been
exceeded.
0023 INVALID STI FILE Invalid or non-existent STI interrupt file.
0024 INVALID STI TIME
Invalid STI interrupt interval (greater than 2550
ms or negative).
0025 TOO MANY JSRs
Excessive stack depth/JSR calls for the STI
routine.
0026 TOO MANY JSRs
Excessive stack depth/JSR calls for an I/O
interrupt routine.
0027 TOO MANY JSRs
Excessive stack depth/JSR calls for the user
fault routine.
0028 INVALID FLT FILE
Invalid or non–existent startup protection” fault
routine file value.
0029 INDEX TOO LARGE
Indexed address reference is outside of entire
data file space (range of B3:0 through the last
file).
002A INDEX TOO LARGE
Indexed address reference is beyond specific
referenced data file.
002B
1
BAD INDRCT FILE Invalid indirect address file number.
002C
1
BAD INDRCT ELEM Invalid indirect address element.
002D
1
BAD INDRCT SUBEL Invalid indirect address subelement.
002E
1
INVALID DII SLOT Invalid DII input slot.
002F
1
INVALID DII FILE Invalid or non-existent DII interrupt file.
0030 SUB NEST TOO DEEP
An attempt was made to jump to one too many
nested subroutine files. This code can also
mean that a program has potential recursive
routines.
0031 UNSUPPORTED INST
An unsupported instruction reference was
detected. Contact Allen-Bradley.
Przeglądanie stron 91
1 2 ... 87 88 89 90 91 92 93 94 95 96 97 ... 115 116

Komentarze do niniejszej Instrukcji