4-30 Configuring Your Compact I/O Series B DeviceNet Adapter
Uploading Configurations
The first time you select a 1769-ADN from RSNetworx when online,
the software will upload the configuration saved in the 1769-ADN.
If there is a mismatch between the saved system keying configuration
and the keys of the actual devices on the 1769 bus, you will see the
following mismatch screen.
The mismatch screen identifies all of the devices in the saved system
keying configuration and all of the actual devices and then highlights
the mismatches. You can choose to use the saved configuration into
the configuration software or use the actual device’s information into
the configuration software.
When you choose to use the saved configuration, the individual I/O
module configurations that had been saved by the 1769-ADN are
used. When you choose to use the actual device’s information, the
individual I/O module configurations from the actual devices are
used.
TIP
You may upload the saved configuration from the
1769-ADN at any time when online by clicking the
right mouse button.