4-18 Configuring Your Compact I/O Series B DeviceNet Adapter
3. From the Advanced Parameters tab, you can configure editable
parameters by selecting from the pull-down menus or directly
typing in the value.
Exact Match: The programmed module type (e.g. 1769-IA16)
and the revision must match exactly with the actual module.
Compatible Module: The programmed module type must
match the actual module, but the revision of the actual
module can be equal or greater than the programmed
revision.
Disable: Any module may be used as a replacement.
Refer to the Comparison Feature section on page 4-29 for an
explanation on the use of this field.
You can configure the Input
Data Size parameter to No
Input Data or 1-6 Words.
You can configure the
Electronic Keying
parameter to Disable
Keying, Exact Match, or
Compatible Module.