Publication 1769-UM001B-EN-P - October 2002
2-24 How Communication Takes Place and I/O Image Table Mapping
Defaults
Factory defaults are the values assigned when you:
• first power up the system, and
• no previous user-programmed stored settings have been applied
Each I/O module has default values associated with it.
Module defaults for I/O size: Factory defaults
(words)
Real time setting
(words)
Description Input Output Input Output
1769-IA8I Individually Isolated 120V
AC Input Module (8 Point)
10 1 0
1769-IA16 120V ac Input Module (16
Point)
10 1 0
1769-IF4 (Series A and B) Analog
Current/Voltage Input Module
(4 Channel)
60 4 0
1769-IM12 240V AC Input Module (12
Point)
10 1 0
1769-IQ16 24V DC Sink/Source Input
Module (16 Point)
10 1 0
1769-OA8 100 to 240V AC Solid State
Output Module (8 Point)
11 0 1
1769-OA16 100 to 240V AC Solid
State Output Module (16 Point)
11 0 1
1769-OA16 100 to 240V AC Solid
State Output Module (16 Point)
11 0 1
1769-OB16P Electronically Protected
Solid-State 24V DC Output Module
11 0 1
1769-OF2 (Series A and B) Analog
Current/Voltage Output Module (2
Channel)
42 0 2
1769-OV16 Solid State 24V DC Sink
Output Module (16 Point)
11 0 1
1769-OW8 AC/DC Relay Output
Module (8 Point)
11 0 1
1769-OW8I Individually Isolated
AC/DC Relay Output Module (8 Point)
11 0 1
1769-OW16 AC/DC Relay Output
Module (16 Point)
11 0 1
1769-OW16 AC/DC Relay Output
Module (16 Point)
21 1 1
1769-IT6 Thermocouple/mV Input
Module
82 4 2