Publication 1769-UM001B-EN-P - October 2002
Configuring Your Compact I/O Series A DeviceNet Adapter 3-7
Using Banks of I/O
Configuration Rules for the Series A Adapter
The Series A adapter must be the first and left-most module in
the system (the first module of Bank 1).
The Series a adapter can communicate with up to 30 modules in
a system.
Each bank of I/O must have its own power supply.
A bank of I/O can have a maximum of 16 modules with a
maximum of eight on either side of the power supply,
depending upon module loading on the supply.
A 1769 I/O power supply has limits in the amount of +5V dc and
+24V dc current it can supply to the modules in its I/O bank.
These limits depend on the catalog number (e.g. 1769-PA2) of
the supply. A bank of modules should not exceed the current
limits of the I/O bank power supply. Refer to the Compact 1769
Expansion I/O Power Supplies Installation Instructions,
publication 1769-5.14.
The maximum amount of current each bank supports in one
direction (either side of the power supply) is: 2A @ 5V dc, 1A @
24V dc.
If another bank of I/O is required, use a bus communication
expansion cable (e.g. 1769-CRL) to link them together. You can
have a maximum of three banks of I/O connected with up to
two communication expansion cables.
Each module type has its own distance rating (the number of
modules from the power supply). Each module must be within
this rating for its type.
The Series A adapter has a distance rating of four, therefore the
adapter must be within four modules of the power supply.
The Series A adapter supports a total of:
180 words of input data from the I/O modules.
180 words of output data for the I/O modules.
724 words of configuration data for the I/O modules.
An end cap/terminator must be on the last I/O bank.