Publication 1769-UM019A-EN-P - October 2008 29
Installation and Wiring Chapter 2
Wire Differential Inputs
Wiring Single-ended Sensor/Transmitter Types
+
–
V in 1+
V in 3+
V in 0+
V/I in 0-
I in 1+
I in 3+
V/I in 1 -
I in 0+
I in 2+
V in 2 +
V/I in 3 -
V/I in 2-
ANLG Com
ANLG Com
V out 1+
I out 1+
V out 0+
I out 0+
+
–
(1) The sensor power supply must be rated Class 2.
Differential
Current
Transmitter
(1)
Differential
Voltage
Transmitter
(1)
Earth Ground the
Shield Locally at
the Module
Belden 8761 Cable (or equivalent)
Earth Ground the Shield
Locally at the Module
+
V in 0+
V/I in 0 -
I in 0+
V in 1+
V/I in 1-
I in 1+
V in 2+
V/I in 2-
I in 2+
ANLG Com
ANLG Com
V in 3+
I out 0+
V out 0+
I out 1 +
V out 1+
V/I in 3-
I in 3+
+
+
-
Current
Transmitter
Sensor/
Transmitter
Power
Supply
(1)
Voltage
Transmitter
Signal
Signal
Ground
Terminal Block
(1) The sensor power supply must be rated Class 2.