9Publication 1769-UM019A-EN-P - October 2008 9
Chapter
1
Overview
Introduction
Module Description
The module converts and digitally stores analog data for retrieval by
controllers, such as the CompactLogix or MicroLogix 1500 controllers.
The module also converts digital data from controllers to provide
analog output data. The module provides the following input and
output types and ranges.
The data can be configured as:
• engineering units.
• scaled-for-PID.
• percent range.
• raw/proportional data.
Module configuration is normally done via the controller’s
programming software. In addition, some controllers support
configuration via the user program. In either case, the module
configuration is stored in the memory of the controller. Refer to your
controller’s user manual for more information.
Topic Page
Module Description 9
System Overview 11
Module Operation 11
Normal and Full Ranges
Signal Type Normal Operating Input Range Full Module Range
Voltage
±10V DC ± 10.5V DC
1…5V DC 0.5…5.25V DC
0…5V DC -0.5…5.25V DC
0…10V DC -0.5…10.5V DC
Current
0…20 mA 0…21 mA
4…20 mA 3.2…21 mA