Publication IASIMP-QS010B-EN-P - October 2009 199
Embedded I/O Chapter 3
Configure the DC Outputs
DC Output Tags
As indicated in the Embedded I/O Tags section on page 192, the tags for the
embedded I/O are located in the Controller Tags folder at the creation of the
packaged controller project.
Tags specific to the use of the DC outputs are described here.
DC Output Tags
The embedded OB16 discrete outputs cannot be configured for
Program and Fault mode output states. If output states are
specified in the OB16 Discrete Outputs Module Properties
dialog box, those states are not implemented in the program.
The DC outputs simply go to 0 (OFF) in the event of the
controller being in Program or Fault modes.
DC Output Input (Status) Tags
DC Output Data Tags