6
Battery Maintenance
Battery for Use with
Packaged Controllers
Use battery 1769-BA with the CompactLogix packaged controllers.
Check Battery Power Level
Use the BATT status indicator to determine the battery power level.
Battery Status Indicator
When the packaged controller is powered, the battery indicator provides
battery power status as described in this table.
If the packaged controller is not powered, you cannot determine the battery
power level.
Topic Page
Battery for Use with Packaged Controllers 237
Check Battery Power Level 237
Estimate 1769-BA Battery Life 238
Store Batteries 238
ATTENTION
The 1769-BA battery is the only battery you can use with the
CompactLogix packaged controllers.
The 1747-BA battery is not compatible with the CompactLogix
packaged controllers and may cause problems if used with a
packaged controller.
If the BATT status indicator is Then
Off The battery has sufficient charge.
On (Red) The battery is 95% discharged and will not
retain memory in the event of a power loss.