Publication IASIMP-QS010B-EN-P - October 2009 215
Embedded I/O Chapter 3
12. Check the storage modes required for your application.
Use this table as a reference when determining the storage modes
required for your application.
13. Click OK.
You have completed configuring your embedded HSC counters.
30Any All
1 Pulse/Internal Direction All
2 Pulse/Internal Direction None
3 Not available
4 0 Pulse/Internal Direction All
1 Pulse/Internal Direction All
2 Pulse/Internal Direction None
3 Pulse/Internal Direction None
Use this Storage mode To achieve this behavior
Store on Rising Z
(1)
(1)
If both a store and preset function are configured, the stored count is captured before the preset operation
takes place.
Store count occurs at on rising edge of Z and is written to
the CtrXStoredCount tag.
(2)
(2)
Where X is the corresponding channel number.
Hold While Z = 1 Hold the counter at its current value while Z = 1.
Preset on Rising Z Preset the count value to the value in the preset word on the
rising edge of Z.
Number of
Counters
Counter Operational Mode Gate or Preset
Functionality