Publication IASIMP-QS010B-EN-P - October 2009 213
Embedded I/O Chapter 3
5. Check Reset Counters if your application requires that the counters and
related tags be reset when the packaged controller is placed in RUN
mode or when the inhibit bit transitions to 0 (OFF).
6. Check Over Current Latch Off if your application requires that outputs
be individually latched off in the event of an over current condition on
the outputs.
Note that if an over current condition occurs and this feature is enabled
(checked), the outputs remain latched off until the ResetBlownFuse bit
transition from 0 to 1.
7. Click the Counter Configuration tab.
8. Click a counter for configuration.