Message Packet Formats
Chapter 5
5-28
Physical Read
This command reads bytes of data from the PC data table or program
memory. Use this command to upload the contents of PLC-2 memory to
your computer.
Use the SIZE field to specify the number of bytes to be read. To specify a
number of PC words, SIZE should be an even value because PC words are
two bytes long.
Command
Format:
Reply Format:
TNSSTSCMD
04
SRCDST
TNSSTSCMD
44
SRCDST
ADDR
DATA
— Max. of 244 Bytes
SIZE
Physical Write
This command writes bytes of data into the PC data table or program
memory. Use this command to download the contents of a computer file
into PLC-2 memory.
Use the SIZE field to specify the number of bytes to be written. To
specify a number of PC words, SIZE should be an even value because PC
words are two bytes long.
Command
Format:
Reply Format:
TNSSTSCMD
03
SRCDST
TNSSTSCMD
43
SRCDST
ADDR
DATA
— Max. of 242 Bytes